Skip to content

The Function of HVAC Control Options

Most HVAC manufacturers provide optional protective controls for the HVAC units they produce. In the past, these controls were standard features installed on every unit, but market pressures toward cost reductions resulted in their removal as standard features/benefits in lieu of currently offering protective control as options.

The protective devices discussed in the following paragraphs are some of the usual controls available for light commercial applications.

A high pressure switch (HPS) and a low pressure switch (LPS) are protective devices for the compressor and refrigeration circuit. The high pressure switch monitors the system for an inoperative outdoor motor, and/or a dirty/restricted condenser (outdoor) coil. The low pressure switch monitors the refrigeration system for a loss of refrigerant charge, and may also be helpful in stopping the evaporator (indoor) coil from freezing up due to a dirty filter or low airflow over the coil. I say "may" because the low pressure switch cut-out setting could be set too low (15-20 lbs.) to be of any help. An evaporator coil could start to form ice at 30 lbs. low pressure charge.

If either one of these switches trip, the HVAC unit will shut down. The control needs to be reset to resume operation. Some switches are reset only from inside the HVAC unit. Others may be reset from the thermostat by turning the thermostat subbase "system" switch off, and back on again, or by doing the same to the HVAC unit's main panel circuit breaker.

A low ambient control (LAC) is useful when high internal heat loads dictate operation in the cooling mode during colder outdoor temperatures. Examples of this would be in an electrical equipment room, telecommunications building, a restaurant, or in loaded computer room applications. Extended operation of the compressor in the cooling mode when the outdoor temperature is less than 65?F can cause the indoor coil to freeze up. The low ambient control cycles the outdoor fan motor in response to refrigerant pressure and conditions. This keeps the system pressures from reaching the condition where icing would occur. Because the outdoor fan "cycles," it may appear to the end user that the condenser motor is defective. Although, this is not the case, an uninformed end user observing a low ambient control in operation could initiate a service call not covered by a first year labor warranty.

A time delay relay (TDR) protects the system against short cycling of the compressor from power interruption, and thermostat problems (due to vibrations, door slamming, or quick "putzing" adjustments by the user). The time delay relay is usually set for a 5 minute delay after the last time the compressor was energized. This device is useful in temporary mobile offices with mercury bulb thermo-stats. It protects the compressor contactor from chattering.

A dirty-filter switch is used to determine when the HVAC unit filter needs changing. It is a simple device that senses a pressure differential across the filter. From a dry set of contacts, it can turn on a light, or even cut the 24 volt power to the stat, shutting the unit off. The dirty-filter switch is manually reset from inside the HVAC unit when the filter is changed.

Start kits or start assist devices are used to help start a single phase compressor with tight bearings, or with a lower than (normal) 230 volt power supply to the compressor. A start kit includes a start capacitor and a potential relay specific to the single phase compressor in the application. A start assist device is all-in-one and is more popular with the service contractors. Some contractors feel a start assist does not provide the same boost as a start kit, but a start assist device usually gets the job done. A start kit is not meant to substitute for providing the proper voltage to the compressor.

If low main power voltage is your problem, first try to boost or improve the power supply to the building. If it can not be improved, a buck/boost transformer should be added to boost the power to the proper level required by the HVAC unit. Adding a buck/boost transformer requires monitoring of the buildings movement from one site to another. The first location may have low voltage, and the next location may not. The transformer boost of the next location may be above the operating range of the HVAC unit, and the buck/boost transformer will need to be removed from the electrical circuit.

Some units have compressor control circuit boards with a time delay relay for short cycling protection. They provide for one retry after the high or low pressure switch trips. This is to insure a condition was not a fluke before shutting the HVAC unit down. Most compressor control circuit boards can be reset inside the building by cycling either the thermostat's system switch or the HVAC unit's main panel circuit breaker to off, and then back on.

Phase monitors are used on three phase HVAC units to protect "scroll" compressors from running back-wards, and eventually seizing up. Running a scroll compressor backwards for more than an hour will pump the oil out of the bottom bearing. An hour is not a very long amount of time, especially when the set up crew does not know to turn off the HVAC unit prior to applying initial power.

Last is the brown out control. It prevents the HVAC unit from starting if the high voltage is not within the operating range of the system (usually 197-253 volts for 230 volt power supply). This control is very useful on mobile offices that continually change locations, because the available local voltage may vary from site to site. When the voltage is not within +10% of the selected voltage, the end user may only know their HVAC unit is not working, not that the voltage to the HVAC unit is too low or too high. While a brown out control would not prevent an HVAC service call, it does protect your asset from abuse. Payment for the HVAC service call then becomes the responsibility of the end user. Include such provision in your lease contracts.

Every optional control has a purpose, and therefore no one control can be recommended over the rest. From time to time, I am asked just which optional controls would be the best, and at the same time be somewhat cost effective. The "cost effective" part is fairly relative and philosophical. If a control can save the compressor from a burn out, a dirty filter from icing the coil, or a low voltage service call, how much is it worth? In other words, if a $ 50-0 control saves a $ 500-900 service call, can your company afford to put that control on every HVAC unit?

Mechanically speaking you should include all of the above items to protect the unit and yourself from problems. That wasn't the question, however. Financially, I would suggest a high and low pressure switch, a compressor control circuit board, and a two inch pleated filter. Then add the other devices as needed for the specific resolution desired. If your site continually has low voltage, add a brown out control. If your three phase HVAC units have scroll compressors, add a phase monitor. If most of your customers are telecommunication shelter users, add a low ambient control, etc.

Contact your mechanical engineer, licensed air conditioning contractor, or equipment supplier for assistance in selecting the correct optional control for your HVAC application.

More from Modular Advantage

A Huge Win for the Modular Construction Industry in Massachusetts

In early February, 2024, the Massachusetts Board of Building Regulations and Standards (BBRS) released its proposed 10th Edition building codes. This draft included several amendments targeting modular construction that would have created an extremely difficult environment for the entire modular industry and could have eliminated the industry entirely in the state.

FEMA Announces Hawaii Housing Plan Using Modular Construction

Utah becomes the second state in the country, following Virginia, to fully adopt ICC/MBI standards 1200 and 1205. MBI will continue to work with leadership in Utah to implement the new program.

Supply and Demand: Solving Canada’s Housing Crisis One Relocatable Housing Unit at a Time

Not only do Moda Modular’s repurposed employee housing solutions cut the emissions related to construction down to nearly zero, but they also keep building materials that are often not biodegradable from slowly decaying in storage facilities.
It’s the classic environmental mantra of reduce, reuse, and recycle, scaled up and applied to building after building.

ICC/MBI Standards 1200 & 1205 Provide Foundation for Utah’s First-Ever State Modular Program

Utah becomes the second state in the country, following Virginia, to fully adopt ICC/MBI standards 1200 and 1205. MBI will continue to work with leadership in Utah to implement the new program.

Repetition, Communication, and Coordination: A QSR Case Study

This modular QSR project seemed like any another modular building on the surface. Inside, it was anything but. The rhythm, the desire to iterate and repeat, and the constant communication between all parties made it stand out.

Modular Architecture: Thinking Outside of the Box with Sara.Ann Logan

At a time when modular buildings were still seen as less than by many in the architecture and construction world, Sara.Ann Logan took the plunge and partnered to launch a design-build firm that designed, built, and constructed modular high-end single-family homes. But even though she could see the value of this kind of construction, it wasn’t universally accepted.

Colorado Developer ‘Attacks’ Attainable Housing Crisis

City, county, and state government bodies are reaching out to Fading West Development, a modular manufacturer and developer in Buena Vista, CO, to learn more about how they are using modular construction to solve the affordable housing crisis in Colorado. Governments are eager to learn how they’ve made modular development successful and profitable while meeting the growing need for affordable housing.

CES Group’s Stuart Cameron Will Convince You the Moon Is Achievable with Modularized MEP

While most people think of construction as a gradually layered process, MEP assemblies—such as the modular ones—tend to provide all-in-one installs, like a car factory. A modular MEP product helps developers, architects, and fellow modular manufacturers reach their goals through early integration and planning. MEP assemblies address all the unseen things like electrical, heating, and plumbing when looking at a finalized building. The very nature of MEP assemblies are crucial to any initial prospectus.

Automation: The Future for Offsite Modular Construction

Offsite modular construction lags far behind other industries in embracing and adopting automation. Some people believe it will decrease jobs. Others feel they’ve done okay without it, so why change? In reality, conventional construction methods simply cannot keep up. Cooper Lane of Brave Control Solutions points to the labor shortage and the housing crisis that’s rampant in Canada, the U.S., and globally.

Seizing the Modular Construction Opportunity

The CSA Public Policy Centre’s new report, Seizing the Modular Construction Opportunity, highlights how innovative modular methods can help to bring various building forms—from single unit housing to complex high-rises—online more quickly. Owing to efficient manufacturing practices and controlled factory environments, modular can achieve completion rates that are 25% to 50% faster than conventional construction approaches.